Generator Relay Model: ATRRELAY

Added in version 19

 

Model Equations and/or Block Diagrams   

Parameters:

u1vsu2 Unit 1 (0) vs Unit 2 (1) preferences switch selection
u3vsu4 Unit 3 (0) vs Unit 4 (1) preferences switch selection
smvslg Small unit (0) vs large unit (1) preference switch selection
lgvs2sm Large unit (0) vs 2 small unit (1) preference switch selection
Monitor Mute mode enabled (1) or disabled (0)
u1delay Unit 1 relay and breaker time delay (sec)
u2delay Unit 2 relay and breaker time delay (sec)
u3delay Unit 3 relay and breaker time delay (sec)
u4delay Unit 4 relay and breaker time delay (sec)
auxdelay Auxiliary load trip time delay (sec)
GenNum If GenNum = 2 then generator to which model is assigned is unit 2 and then Gen2 would represent unit 1, and so on. Also NOTE that the results of the gens are now going to be in a different order if the GenNum is not 1.
LeaveOneOn LeaveOneOn: Set to a non-zero value to force at least one generator in this to remain online when a tripping command is sent. The generator with the smallest initial MW output will remain on.